Water Control Solutions

Fire Protection Valves
main_smRelief-Valves_Lobby

The NFPA 13, UL, FM and Manufacturer Requirements for Pressure Relief Valves Downstream of Installed Pressure Reducing Valves

Paul Goldsmith
By
Paul Goldsmith
30 Dec 2019
)
Last updated: 31 May 2022

The design of fire protection systems is a complicated process that requires an integrated approach and a high level of expertise. System designers and engineers need to take a large number of factors into account while also understanding and complying with stringent local, regional, and international standards. 

In this blog post, we will be discussing one of the components in these systems – for the Installation of Sprinkler Systems, UL and FM standards, and manufacturer recommendations, a pressure relief valve is required at the outlet, downstream of all installed pressure reducing valves, as part of the pressure regulating equipment in fire protection systems.

Do pressure reducing valves guarantee a set outlet pressure?

Pressure reducing valves are used to protect pressure-sensitive piping, instrumentation, and devices in fire protection systems against overpressure conditions downstream. In normal conditions, they perform this function well. However, sometimes in exceptional hydraulic scenarios, the pressure reducing valve is momentarily unable to maintain the set outlet pressure.

There are a few common causes for overpressure events related to pressure reducing valves:

  1. The first and most dangerous is water hammer, which among other things, may be caused by the overly quick closing of a valve downstream (a typical occurrence with fire hose nozzle and hydrant valves). As this pressure surge occurs downstream of the pressure reducing valve, the valve will not be able to compensate and as a result, there will be overpressure which is sometimes quite extreme.
  2. A sudden increase or spike in pressure experienced at pump start-up, or as a result of quick operating valves. With such fast changes in pressure, the pressure reducing valve (especially if it has a larger diameter) cannot react quickly enough to prevent a sudden pressure wave momentarily travelling downstream.
  3. A pressure reducing valve failing to seal. This can be caused by firewater debris getting trapped on the valve's sealing surface or even just wear-and-tear that prevents a watertight seal required in static no flow conditions. This allows for a gradual leak and build-up of high pressure downstream.
  4. In certain cases during static no flow conditions, the pressure downstream of a pressure reducing valve can increase as a result of a rise in temperature. This is because the "Thermal Expansion" of the water and air within the piping is greater than the thermal expansion of the pipe itself, and thus causing a rise in pressure in the piping.

While these events are few and far between, they do happen and the system needs to be prepared in order to prevent overpressure conditions when they occur. For these reasons, it is accepted standard practice and authorities require that a quick acting pressure relief valve be installed downstream of the pressure reducing valve as a safeguard against any inadvertent pressure rises downstream.

 

'Pressure relief valves offer an extra level of safety against overpressure conditions

Pressure Relief valves are safety devices that are designed to quickly relieve overpressure in a fire protection system. Pressure relief valves are designed to open at a preset pressure threshold to drain the excess water pressure to the atmosphere or to a sump. Once the excess water pressure has been released and the line pressure drops to below the threshold once again, the relief valve returns to seal drip tight.

What to look for when selecting pressure relief valves for pressure reducing valves in fire protection systems

When selecting pressure relief valves for fire protection systems, it’s important to take the following factors into account:

  • Sizing. While the NFPA and UL and FM standards stipulate the use of a minimum size pressure relief valve downstream, this is a minimum requirement and knowledgeable designers and manufacturers often recommend a larger size valve. The size should depend on the line size and working conditions. In the case of slow leaks, a smaller relief valve is sufficient. However, in the case of sudden pressure buildups or surges, a bigger relief valve is often required to release larger amounts of water quickly. For these reasons, it’s important to perform an analysis of system requirements and potential capacity of overpressure events when selecting the size of the pressure relief valves. The following is the BERMAD sizing table, which is applicable for normal or typical conditions:

Minimum Recommended Relief Valve Sizing Table for Pressure Reducing Valves

 

Pressure Reducing Valve  or Line Size in. (mm)

1.5”
(40)

2"
(50)

2.5"
(65)

3”
(80)

4”
(100)

6”
(150)

8”
(200)

10”
(250)

12”
(300)

14"
(350)

16"
(400)

Recommended Relief Valve Size in. (mm)

3/4"
(20)

3/4"
(20)

3/4"
(20)

3/4"
(20)

2"
(50)

3"
(80)

3"
(80)

4"
(100)

2 x 4"
(2x100)

2 x 4"
(2x100)

2 x 4"
(2x100)

 

blog_images_ressure Relief Valves4new

  • Reliability. As pressure relief valves are a safety requirement, it’s important to choose a pressure relief valve that is developed and manufactured by a well-known and reliable company. In addition, system developers should check that the pressure relief valve complies and is certified with all of the compulsory standards and is approved and listed by the accepted industry institutions.
  • Opening characteristics. Relief valves can be divided into two main types, direct-acting and pilot-operated. Direct acting valves use a spring above the pressure sensing area. When the pressure force is higher than that of the spring, the valve will open. Pilot operated relief valves use a large main valve that will open when the auxiliary pilot senses a pressure higher than the set point.
     
    • The opening degree of direct-acting relief valves is somewhat limited by being directly related to the line pressure and the pressure range. These valves are quick opening, economical and simple in construction. As such, they are considered the valve of choice for lower relief flow requirements.

      Also bear in mind that because direct-acting relief valves open directly against the main spring, their size and pressure range is limited. The reason for this is that with larger diameters and higher pressures, the spring becomes too big, cumbersome, and uneconomical.

    • Pilot-operated relief valves are faster to reach full opening and have a steeper opening curve, which is more suitable for larger piping that may need fast high-capacity relief and where the valve needs to fully open quickly, as may be the case where there is a threat of surge conditions.
  • Accuracy. Both types of relief valves, if carrying the aforementioned certification, will have an accuracy that meets the necessary tolerance for pressure reducing relief:
     
    • Direct-acting relief valves - for use where a small flow capacity is required. These valves have a fast and accurate cracking point, but a limited opening characteristic. They are usually smaller and suited to low capacity relief duty.
    • Pilot-operated relief valves - for use in higher capacity and pressure applications, are considered more accurate across varied pressures and flows as the pilot's sensing point is less exposed to the high flows during relief duty. Once the set pressure has been exceeded then these valves will continue to open fully until pressure returns to below the set pressure.

BERMAD’s pressure relief valve solutions

BERMAD offers industry-proven relief valves that are designed specifically for advanced fire protection systems and comply with the latest industry standards. These solutions include the BERMAD FP-3HC-0 direct-acting relief valves, which are ideal for controlling pressure and preventing overpressure conditions in fire protection systems where lower relief flows suffice. They are available in a wide variety of corrosion-proof materials to suit diverse media and environmental conditions; and their robust design ensures a long and reliable service life. 

 

The BERMAD FP-43T and FP-430-UF pilot-operated relief valves are elastomeric-type globe valves that are rolling-diaphragm actuated with an integral, solid and resilient seal. They are used for overpressure prevention for larger piping, water flow in fire protection systems; and are manufactured from various materials and coatings to suit all types of municipal, industrial, onshore and offshore specifications.

 

blog_images_ressure Relief Valves4-2

 

 

To find out more about our pressure relief valves and other fire-protection products, visit our website.

Need fire protection design assistance?

BERMAD engineers are available to provide you with expert guidance in fire protection applications and systems. To learn more, click here to contact a BERMAD representative in your region.

Dealing with water pressure surge and water hammer in fire protection system - white paper

Topics: Fire Protection, Fire Pump, Circulation relief valve fire pump

Paul Goldsmith

Written by Paul Goldsmith

Paul has worked at BERMAD since 1998 as a Test Engineer for Research and Development, Product Management and in Marketing. He holds a degree in Water Management and Hydraulic Engineering from the Ruppin Academic Center.

New call-to-action

Recent Posts

NEVER MISS A STORY